EasyManua.ls Logo

Danfoss VLT FC 100 Series

Danfoss VLT FC 100 Series
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[84] SL Digital Output E See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [42]
Set dig. out. E
high
is executed. The input will go low whenever the Smart Logic Action [36]
Set dig. out. E low
is executed.
[85] SL Digital Output F See par. 13-52
SL Control Action
. The input will go high whenever the Smart Logic Action [43]
Set dig. out. F
high
is executed. The input will go low whenever the Smart Logic Action [37]
Set dig. out. F low
is executed.
[160] No alarm The output is high when no alarm is present.
[161] Running reverse The output is high when the frequency converter is running counter clockwise (the logical product of the status
bits ‘running’ AND ‘reverse’).
[165] Local reference active The output is high when par. 3-13
Reference Site
= [2] Local or when par. 3-13
Reference Site
= [0]
Linked to
hand auto
at the same time as the LCP is in Hand on mode.
[166] Remote reference ac-
tive
The output is high when par. 3-13
Reference Site = Remote
[1] or
Linked to hand/auto
[0] while the LCP is in
[Auto on] mode.
[167] Start command active The output is high when there is an active Start command (i.e. via digital input bus connection or [Hand on] or
[Auto on], and no Stop or Start command is active.
[168] Drive in hand mode The output is high when the frequency converter is in Hand on mode (as indicated by the LED light above [Hand
on].
[169] Drive in auto mode The output is high when the frequency converter is in Hand on mode (as indicated by the LED light above [Auto
on].
[180] Clock Fault The clock function has been reset to default (2000-01-01) because of a power failure.
[181] Preventive Mainte-
nance
One or more of the Preventive Maintenance Events programmed in par. 23-10, Preventive Maintenance Item,
has passed the time for the specified action in par. 23-11, Maintenance Action.
[190] No-Flow A No-Flow situation or Minimum Speed situation has been detected if enabled in
Minimum Speed Detection
. par.
22-21 and/or
No-Flow Detection
, par. 22-22.
[191] Dry Pump A Dry Pump condition has been detected. This function must be enabled in par. 22-26, Dry Pump Function.
[192] End of Curve A pump running with max. speed for a period of time without reaching the set pressure has been detected. To
enable this function please see
par. 22-50 End of Curve Function
.
[193] Sleep Mode The frequency converter/system has turned into sleep mode. See
Sleep mode
, par. 22-4*.
[194] Broken Belt A Broken Belt condition has been detected. This function must be enabled in par. 22-60, Broken Belt Detection.
[195] Bypass Valve Control The bypass valve control (Digital / Relay output in the frequency converter) is used for compressor systems to
unload the compressor during start-up by using a bypass valve. After the start command is given the bypass
valve will be open until the frequency converter reaches
Motor speed low limit
, par. 4 -11) . After the limit has
been reached the bypass valve will be closed, allowing the compressor to operate normally. This procedure will
not be activated again before a new start is initiated and the frequency converter speed is zero during the
receiving of start signal.
Start Delay
, par. 1-71 can be used in order to delay the motor start. The Bypass valve
control principle:
[196] Fire Mode The frequency converter is operating in Fire Mode. See 24-0*
Fire Mode
.
[197] Fire Mode was act. The frequency converter has been operating in Fire Mode, but is now back in normal operation.
[198] Drive Bypass To be used as signal for activating an external electromechanical bypass switching the motor direct on line. See
24-1*
Drive Bypass
.
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
71
3

Other manuals for Danfoss VLT FC 100 Series

Related product manuals