5-94 Pulse Out #27 Timeout Preset
Range: Function:
0 %
*
[0 - 100 %]
Contains the frequency to apply to the digital output terminal 27, when it is configured as [Bus Controlled Time-
out] and timeout is detected.
5-95 Pulse Out #29 Bus Control
Range: Function:
0 %
*
[1 - 100 %]
Contains the frequency to apply to the digital output terminal 29, when it is configured as [Bus Controlled].
5-96 Pulse Out #29 Timeout Preset
Range: Function:
0 %
*
[1 - 100 %]
Contains the frequency to apply to the digital output terminal 29, when it is configured as [Bus Controlled Time-
out] and timeout is detected
5-97 Pulse Out #X30/6 Bus Control
Range: Function:
0 %
*
[1 - 100 %]
Contains the frequency to apply to the digital output terminal 27, when it is configured as [Bus Controlled.
5-98 Pulse Out #X30/6 Timeout Preset
Range: Function:
0 %
*
[1 - 100 %]
Contains the frequency to apply to the digital output terminal 6, when it is configured as [Bus Controlled Timeout]
and timeout is detected.
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®