[3]
*
Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter reverse function via the terminals (digital input) and/or via the fieldbus.
[0]
*
Digital input
[1] Bus Activates Reverse command via the serial communication port or fieldbus option.
[2] Logic AND Activates Reverse command via the fieldbus/serial communication port, AND additionally via one of the digital
inputs.
[3] Logic OR Activates Reverse command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the fieldbus.
[0] Digital input
[1] Bus Activates the set-up selection via the serial communication port or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one of the digital
inputs.
[3]
*
Logic OR Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input
[1] Bus Activates Preset Reference selection via the serial communication port or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3]
*
Logic OR Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of the digital
inputs.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and control word
.
VLT
®
HVAC Drive Programming Guide 3. Parameter Description
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
95
3