EasyManuals Logo

Danfoss VLT FC 100 Series Programming Guide

Danfoss VLT FC 100 Series
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
3.9.7. 8-7* BACnet
BACnet configuration
8-70 BACnet Device Instance
Range: Function:
1
*
[0 - 4194304]
Enter a unique ID number for the BACnet device.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-72 MS/TP Max Masters
Range: Function:
127
*
[0 - 127]
Define the address of the master which holds the highest address in this network. Decreasing this value optimises
polling for the token.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-73 MS/TP Max Info Frames
Range: Function:
1
*
[1 - 65534]
Define how many info/data frames the device is allowed to send while holding the token.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-74 "I-Am" Service
Option: Function:
[0]
*
Send at power-up
[1] Continuously Choose whether the device should send the "I-Am" service message only at power-up or continuously with an
interval of approx. 1 min.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-75 Initialisation Password
Range: Function:
Size
related
*
[0 - 0]
Enter the password needed for execution of Drive Re-initialisation from BACnet.
3. Parameter Description VLT
®
HVAC Drive Programming Guide
96
MG.11.C5.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals