3.9.7. 8-7* BACnet
BACnet configuration
8-70 BACnet Device Instance
Range: Function:
1
*
[0 - 4194304]
Enter a unique ID number for the BACnet device.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-72 MS/TP Max Masters
Range: Function:
127
*
[0 - 127]
Define the address of the master which holds the highest address in this network. Decreasing this value optimises
polling for the token.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-73 MS/TP Max Info Frames
Range: Function:
1
*
[1 - 65534]
Define how many info/data frames the device is allowed to send while holding the token.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-74 "I-Am" Service
Option: Function:
[0]
*
Send at power-up
[1] Continuously Choose whether the device should send the "I-Am" service message only at power-up or continuously with an
interval of approx. 1 min.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-75 Initialisation Password
Range: Function:
Size
related
*
[0 - 0]
Enter the password needed for execution of Drive Re-initialisation from BACnet.
3. Parameter Description VLT
®
HVAC Drive Programming Guide
96