Why is the Danfoss Controller mains current imbalance greater than 3%?
- LlhenryAug 27, 2025
A mains current imbalance greater than 3% in your Danfoss Controller setup can stem from issues with the mains power supply. If the imbalanced leg follows the wire, it suggests a power problem, so check the mains power supply. Alternatively, the frequency converter itself might be faulty. If the imbalance leg remains on the same input terminal, it points to a problem with the unit, and you should contact the supplier.