Why is my Danfoss DC Drives motor not running?
- SstevenyoungSep 23, 2025
If the motor is not running on your Danfoss DC Drives, consider the following: * Ensure the service switch is not open and the motor connection is present. Connect the motor and check the service switch. * If using a 24 V DC option card, ensure mains power is applied to run the unit. * Check if the LCP Stop is active. Press [Auto On] or [Hand On] (depending on the operation mode) to run the motor. * Verify a start signal is present. Apply a valid start signal to start the motor. * Ensure the motor coast signal is not active. Apply 24 V on terminal 27 or program this terminal to No operation. * The reference signal source may be incorrect. Program the correct settings.














