What to do if Danfoss Media Converter motor is not running?
- FfryejoseSep 3, 2025
If the motor isn't running, it might be due to several reasons. Check if the service switch is open or if there's a missing motor connection; connect the motor and check the service switch. If you have a 24 V DC option card, ensure line power is applied to run the unit. If the LCP Stop is active, press [Auto On] or [Hand On], depending on the operation mode, to start the motor. Ensure a valid start signal is applied. If the motor coast signal is active, apply 24 V on terminal 27 or program this terminal to No operation. Finally, check that the reference signal source is correctly programmed, including wiring and scaling of terminals.