OL1 - Single Motor OL1 - Dual Motor OL2 - Dual Motor CMS - M4 & M5 MT1 TB 0R LUG (ECB)
Type Code Char CHAR 20 CHAR 20 CHAR 20 CHAR 20 CHAR 13&14&18
Type Code S D D C NO&D
[HP]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
Maximum Wire Size
[AWG]
0.50 8 N/A N/A 10 12
0.75 8 N/A N/A 10 12
1 8 N/A N/A 10 12
1.5 8 8 8 10 12
2 8 8 8 10 12
3 8 8 8 10 12
5 8 8 8 10 4
7.5 8 8 8 8 4
10 8 8 8 8 4
15 1/0 8 8 1/0 4
20 1/0
1/0 (15-30HP) 8 (0.5-10HP)
1/0 4
8 (0.5-10HP) 8 (0.5-10HP)
25 1
1 (15-30HP) 8 (0.5-10HP)
1/0 1
8 (0.5-10HP) 8 (0.5-10HP)
30 1 1 (15-30HP) 8 (0.5-10HP) 1/0 1
40 4/0
1/0 (15-30HP) 8 (0.5-10HP)
4/0 250KCM
1/0 (15-30HP) 1/0 (15-30HP)
50 4/0
4/0 (40-60HP) 8 (0.5-10HP)
4/0 250KCM1/0 (15-30HP) 8 (0.5-10HP)
1/0 (15-30HP) 1/0 (15-30HP)
60 4/0
4/0 (40-60HP) 8 (0.5-10HP)
4/0 250KCM4/0 (40-60HP) 1/0 (15-30HP)
1/0 (15-30HP) 1/0 (15-30HP)
Table 3.11 230 V Max Wire - Output