1-24 Motor Current (I
m.n
)
Range: Function:
M-type de-
pendent*
[0.01 - 26.00 A] Enter motor current from nameplate data.
1-25 Motor Nominal Speed (n
m.n
)
Range: Function:
M-type De-
pendent*
[100 - 9999 RPM] Enter motor nominal speed from nameplate data.
1-29 Automatic Motor Tuning (AMT)
Option: Function:
Use AMT to optimize motor performance.
NB!
This parameter cannot be changed while motor runs.
1. Stop the frequency converter – make sure motor is at standstill
2. Choose [2] Enable AMT
3. Apply start signal
– Via LCP: Press Hand On
- Or in Remote On mode: Apply start signal on terminal 18
[0] * Off AMT function is disabled.
[2] Enable AMT AMT function starts running.
NB!
To gain optimum tuning of frequency converter, run AMT on a cold motor.
3-02 Minimum Reference
Range: Function:
0.00* [-4999 - 4999] Enter value for minimum reference.
The sum of all internal and external references are clamped (limited) to the minimum reference
value, par. 3-02.
3-03 Maximum Reference
Range: Function:
Maximum Reference is adjustable in the range Minimum Reference - 4999.
50.00* [-4999 - 4999] Enter value for Maximum Reference.
The sum of all internal and external references are clamped (limited) to the maximum reference
value, par. 3-03.
VLT
®
Micro Drive FC 51 Operating Instructions 4 Programming
MG.02.A4.02 - VLT
®
is a registered Danfoss trademark
21