7 Troubleshooting
No. Description Warning Alarm Trip Lock Error Cause of Problem
2 Live zero error X X     Signal on terminal 53 or 60 is less than 50% of value set in par. 6-10, 6-12 and 6-22.
4
Mains phase loss
1)
X X X   Missing phase on supply side, or too high voltage imbalance. Check supply voltage.
7
DC over voltage
1)
X X     Intermediate circuit voltage exceeds limit.
8
DC under voltage
1)
X X     Intermediate circuit voltage drops below “voltage warning low” limit.
9 Inverter overloaded X X     More than 100% load for too long.
10 Motor ETR over temperature X X     Motor is too hot due to more than 100% load for too long.
11 Motor thermistor over temperature X X     Thermistor or thermistor connection is disconnected.
12 Torque limit X       Torque exceeds value set in either par. 4-16 or 4-17.
13 Over Current X X X   Inverter peak current limit is exceeded.
14 Earth fault   X X   Discharge from output phases to ground.
16 Short Circuit   X X   Short-circuit in motor or on motor terminals.
17 Control word timeout X X     No communication to frequency converter.
25 Brake resistor short-circuited   X X   Brake resistor is short-circuited, thus brake function is disconnected.
27 Brake chopper short-circuited   X X   Brake transistor is short-circuited, thus brake function is disconnected.
28 Brake check   X     Brake resistor is not connected/working
29 Power board over temp X X X   Heat-sink cut-out temperature has been reached.
30 Motor phase U missing   X X   Motor phase U is missing. Check the phase.
31 Motor phase V missing   X X   Motor phase V is missing. Check the phase.
32 Motor phase W missing   X X   Motor phase W is missing. Check the phase.
38 Internal fault   X X   Contact local Danfoss supplier.
47 Control Voltage Fault X X X   24 V DC may be overloaded.
51 AMT check U
nom
 and I
nom
  X     Wrong setting for motor voltage and/or motor current.
52 AMT low I
nom
  X     Motor current is too low. Check settings.
59 Current limit X       VLT overload.
63 Mechanical Brake Low   X     Actual motor current has not exceeded “release brake” current within “start delay” time
window.
80 Drive Initialised to Default Value   X     All parameter settings are initialized to default settings.
84 The connection between drive and LCP is lost       X No communication between LCP and frequency converter
85 Button disabled       X See parameter group 0-4* 
LCP
86 Copy fail       X An error occurred while copying from frequency converter to LCP or vice versa.
87 LCP data invalid       X Occurs when copying from LCP if the LCP contains erroneous data - or if no data was
uploaded to the LCP.
88 LCP data not compatible       X Occurs when copying from LCP if data are moved between frequency converters with
major differences in software versions.
89 Parameter read only       X Occurs when trying to write to a read-only parameter.
90 Parameter database busy       X LCP and RS485 connection are trying to update parameters simultaneously.
91 Parameter value is not valid in this mode       X Occurs when trying to write an illegal value to a parameter.
92 Parameter value exceeds the min/max limits       X Occurs when trying to set a value outside the range.
nw run Not While RUNning       X Parameter can only be changed when the motor is stopped.
Err. A wrong password was entered       X Occurs when using a wrong password for changing a password-protected parameter.
1)
 These faults may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.
Table 7.1: Warnings and Alarms
Code list
VLT
®
 Micro Drive FC 51 Operating Instructions 7 Troubleshooting
MG.02.A4.02 - VLT
®
 is a registered Danfoss trademark
59
  7