6-22  Terminal 60 Low Current
Range: Function:
  [0.00 - 19.99 mA] Normally set to 0 or 4 mA.
6-23  Terminal 60 High Current
Range: Function:
  [0.01 - 20.00 mA] Normally (default) set to 20 mA.
6-24  Terminal 60 Low Feedback Value
Range: Function:
  [-4999 - 4999] Value corresponding to P. 6-22 setting.
6-25  Terminal 60 High Feedback Value
Range: Function:
  [-4999 - 4999] Value corresponding to P. 6-23 setting.
6-26  Terminal 60 Filter Time Constant
Range: Function:
  [0.01 - 10.00 s] Filter for suppressing electrical noise.
7-20  Process CL Feedback Resource
Range: Function:
  [] Choose [2] analog input 60.
7-30  Process PI Normal/Inverse
Range: Function:
  [] Most PI controllers are “Normal”.
7-31  Process PI Anti Windup
Range: Function:
  [] Leave 
Enabled
 normally.
7-32  Process PI Start Speed
Range: Function:
  [0.0 - 200.0 Hz] Choose expected normal running speed.
7-33  Process PI Proportional Gain
Range: Function:
  [0.00 - 10.00] Enter the P-factor.
7-34  Process PI Integral Time
Range: Function:
  [0.10 - 9999.00 s] Enter the I-factor.