3.5.5 Recommendation of Fuses
Table 4: Fuses
FC 51
Maximum fuses non–UL
kW
Type gG
1x200–240 V
0K18–0K37
16A
0K75
25A
1K5
35A
2K2
50A
3x380–480 V
0K37–0K75
10A
1K5
16A
2K2
20A
3K0
40A
4K0
40A
5K5
40A
7K5
40A
11K0
63A
15K0
63A
18K5
80A
22K0
80A
3.6 Connecting to Mains and Motor
The drive is designed to operate all standard 3-phased asynchronous motors.
The drive is designed to accept mains/ motor cables with a maximum cross-section of 4 mm
2
/10 AWG (M1, M2, and M3), and a
maximum cross-section of 16 mm
2
/6 AWG (M4 and M5).
AQ348848915086en-000101 / 130R0943 | 11Danfoss A/S © 2020.09
Installation
VLT® Micro Drive FC 51
Operating Guide

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)