Wrong setting for motor voltage and/or motor current.
The motor current is too low. Check the settings.
Actual motor current has not exceeded the release
brake current within the start delay time window.
Drive initialized to de-
fault value
All parameter settings are initialized to default settings.
The connection be-
tween drive and LCP is
lost
No communication between LCP and drive.
See parameter group 0-4* LCP.
An error occurred while copying from drive to LCP, or
from LCP to drive.
Occurs when copying from LCP if the LCP contains er-
roneous data - or if no data was uploaded to the LCP.
Occurs when copying from LCP if data are moved be-
tween drives with major dierences in software ver-
sions.
Occurs when trying to write to a read-only parameter.
LCP and RS485 connection are trying to update param-
eters simultaneously.
Parameter value is not
valid in this mode
Occurs when trying to write an illegal value to a param-
eter.
Parameter value ex-
ceeds the minimum/
maximum limits
Occurs when trying to set a value outside the range.
Parameters can only be changed when the motor is
stopped.
A wrong password was
entered
Occurs when using a wrong password for changing a
password-protected parameter.
1
These faults are caused by mains distortions. Install a Danfoss line lter to rectify this problem.