6 Application Examples
6.1.1 Start/Stop
Terminal 18 = start/stop 5-10 Terminal 18 Digital Input [8]
Start
Terminal 27 = No operation 5-12 Terminal 27 Digital Input
[0] No operation (Default coast inverse
5-10 Terminal 18 Digital Input = Start (default)
5-12 Terminal 27 Digital Input = coast inverse
(default)
Illustration 6.1 Terminal 37: Available only with Safe Stop
Function
6.1.2 Pulse Start/Stop
Terminal 18 = start/stop 5-10 Terminal 18 Digital Input [9]
Latched start
Terminal 27= Stop 5-12 Terminal 27 Digital Input [6] Stop
inverse
5-10 Terminal 18 Digital Input = Latched start
5-12 Terminal 27 Digital Input = Stop inverse
Illustration 6.2 Terminal 37: Available only with Safe Stop
Function
Application Examples
VLT
®
Refrigeration Drive Design Guide
82 MG16G102 - VLT
®
is a registered Danfoss trademark
6
6