EasyManuals Logo

Danfoss VLT Design Guide

Danfoss VLT
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
sequence starts over again from event [1] / action [1]. The
illustration shows an example with three events / actions:
Illustration 6.4
6.1.7 SLC Application Example
One sequence 1 Start ramp up run at reference speed 2 sec ramp
down and hold shaft until stop.
Illustration 6.5
Set the ramping times in 3-41 Ramp 1 Ramp Up Time and
3-42 Ramp 1 Ramp Down Time to the wanted times
t
ramp
=
t
acc
×
n
norm
(
par
. 1 25
)
ref
RPM
Set term 27 to No Operation (5-12 Terminal 27 Digital Input)
Set Preset reference 0 to first preset speed (3-10 Preset
Reference [0]) in percentage of Max reference speed
(3-03 Maximum Reference). Ex.: 60%
Set preset reference 1 to second preset speed (3-10 Preset
Reference [1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in 13-20 SL
Controller Timer [0]. Ex.: 2 sec.
Set Event 1 in 13-51 SL Controller Event [1] to True [1]
Set Event 2 in 13-51 SL Controller Event [2] to On Reference
[4]
Set Event 3 in 13-51 SL Controller Event [3] to Time Out 0
[30]
Set Event 4 in 13-51 SL Controller Event [4] to False [0]
Set Action 1 in 13-52 SL Controller Action [1] to Select preset
0 [10]
Set Action 2 in 13-52 SL Controller Action [2] to Start Timer
0 [29]
Set Action 3 in 13-52 SL Controller Action [3] to Select preset
1 [11]
Application Examples
VLT
®
Refrigeration Drive Design Guide
84 MG16G102 - VLT
®
is a registered Danfoss trademark
6
6

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals