Programming
207 Ramp-up time 1
(RAMP-UP TIME 1)
Value:
0.02 - 3600.00 sec
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
The ramp-up ti me is the accelerati on time from 0
Hz to the rated motor frequency f
M,N
(parameter
104 Motor frequency, f
M,N
). It is assumed that the
output current will not reach the current limit (set
in param eter 2 21 Current limit I
LIM
).
Description of choice:
Set the required ramp-up time.
208 Ramp-down time 1
(RAMPDOWNTIME1)
Value:
0.02 - 3600.00 sec
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
The ramp-down time is the deceleration time
from the rated motor frequency f
M,N
(parameter
104 Motor frequency, f
M,N
)to0Hz,provided
no overvoltage arises in the inverter because of
generating operation of the motor.
Description of choice:
Set the required ramp-down time.
209 Ramp-up time 2
(RAMPUPTIME2)
Value:
0.02 - 3600.00 sec.
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
See description of parameter 207 Ramp-up t ime 1.
Description of choice:
Set the required ramp-up t ime. Shift from ramp 1 to
ramp 2 by activating Ramp 2 viaadigitalinput.
210 Ramp-down time 2
(RAMPDOWNTIME2)
Value:
0.02 - 3600.00 sec.
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
See descript ion of parame ter 208 Ramp-down time 1.
Description of choice:
Set the required ramp-down time. Shift from ramp 1
to ramp 2 by activating Ramp 2 via a digital input.
211 Jog ramp time
(JOG RAMP TIME)
Value:
0.02 - 3600.00 sec.
3.00 sec (VLT 2803-2875)
10.00 sec (VLT 2880-2882)
Function:
The jog ramp t ime is the acceleration/deceleration
time from 0 Hz to the rated m otor frequency f
M,N
(parameter 104 Motor frequency, f
M,N
). It is assumed
that the output current will not reach the current
limit(setinparameter221Current limit I
LIM
).
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.E9.02 - VLT is a registered Danfoss trademark
81

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VT2800 Series and is the answer not in the manual?

Danfoss VT2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVT2800 Series
CategoryController
LanguageEnglish

Related product manuals