EasyManuals Logo

Danfoss VT2800 Series User Manual

Danfoss VT2800 Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
VLT
®
2800 Series
This table shows what the output frequency is:
Preset
ref., msb
Preset
ref., lsb
Selection
of Setup
Output
frequency[Hz]
0 0 0 2.5
0 1 0 5
1 0 0 10
1 1 0 17.5
0 0 1 20
0 1 1 25
1 0 1 35
1 1 1 50
Connection of mechanical brake
Use of the relay for 230V AC brake
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coast ing stop inverted [2]
Par. 323 Re lay output = Mechanical
brake control [25]
Mechanical brake control [25] = 0 => Brake is closed.
Mechanical brake control [25] = 1 => The
brake is open.
See more detailed parameter settings under
Control of mechanical brake .
NB!:
Do not use the internal relay for DC brakes
or brake voltages > 250 V.
Counter stop via terminal 33
The start signal (terminal 18) must be active, i.e. logical
1, until the output frequency is equal to the reference.
The start signal (terminal 18 = logical 0) must then be
removed before the counter value in parameter 344
has managed to stop the VLT frequency converter.
Par. 307 Digital input = Pulse input [30]
Par. 343 Precise stop function = Counter
stop with reset [1]
Par. 344 Counter value = 100000
Use of internal PID-controller - closed
loop process control
1. Connect the frequency converter to mains
and motor cables as usual.
2. Connect transmitter (feedback signal) to + terminal
12 and - terminal 60 (applies to 2-wire transmitters
4-20 mA). (Connect transmitters with 0-10 V DC
to + terminal 53 and - terminal 55).
NB!:
Connect terminal 55 as - and terminal 60
as + for current signal (0/4-20 mA) and
terminal 53-55 for voltage signal (0-10 V DC) if
transmitters with separate voltage supply a re used.
3. Connect the start signal between terminal 1 2
and 18, 12-27 must be connected or set to
no function (parameter 304 = 0).
4. Set all parameters in the Quick M enu and enter
the Main Menu (to enter the Main Me nu: Press
Quick Menu and + simultaneously).
5. Set the following parameters:
100 = Proc ess controller closed loop [3]
101 = Variable torque medium [3]
If used with centrifugal pumps and fans.
308 = Feedback [2] (for 0-10 V DC transmitters) o
r
314 = Fe edback [2] (for 4-20 mA transmitters)
414 = Minimum feedback scaling, must be set
to the minimum feedb ack value
415 = Ma ximum feedba ck scaling, must be set
to the maximum feedback value
Example: Pressure transmitter 0-10 bar:
414 = 0 and 415 = 10
416 = Proce ss units: As shown on the local
control panel (example: bar [4])
437 = Normal [0]: The output frequency should be
reduced when the feedback signal increases
Inverse [1]: The output frequency should increase
when the feedback signal increases
440 = Proport ional gain (P-gain) 0.3-1.0
(experienced value)
MG.28.E9.02 - VLT is a registered Danfoss trademark
58

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VT2800 Series and is the answer not in the manual?

Danfoss VT2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVT2800 Series
CategoryController
LanguageEnglish

Related product manuals