VLT
®
2800 Series
Introduction to VLT
2800
This section makes it easier for you to specify and
order a VLT 2800.
Choice of frequency converter
The frequency converte r must be chosen on the
basis of the present motor current at maximum
loading of the unit. The frequency converter’s rated
output current I
INV.
must be equal to or greater than
the required motor current.
Mains voltage
VLT2800is
available for two mains voltage
ranges: 200-240 V and 380-480 V.
Select whether the frequency converter is
connected to a mains voltage of:
- 1 x 220 - 240 V single-phase A C voltage
- 3 x 200 - 240
V three-phase AC voltage
- 3 x 380 - 480 V three-phase AC voltage
1 x 220 - 240 Volt mains voltage
Typical s haft ou tput
P
INV.
M ax. constant output
current I
INV.
M ax. constant outp ut power
at 230 V S
INV.
Type [kW] [HP] [A] [kVA]
2803 0.37 0.5 2.2 0.9
2805 0.55 0.75 3.2 1.3
2807 0.75 1.0 4.2 1.7
2811 1.1 1.5 6.0 2.4
2815 1.5 2.0 6.8 2.7
3 x 200 - 240 Volt mains voltage
Typical s haft ou tput
P
INV.
M ax. constant output
current I
INV.
M ax. constant outp ut power
at 230 V S
INV.
Type [kW] [HP] [A] [kVA]
2803 0.37 0.5 2.2 0.9
2805 0.55 0.75 3.2 1.3
2807 0.75 1.0 4.2 1.7
2811 1.1 1.5 6.0 2.4
2815 1.5 2.0 6.8 2.7
2822 2.2 3.0 9.6 3.8
2840 3.7 5.0 16.0 6.4
MG.28.E9.02 - VLT is a registered Danfoss trademark
9