Display and menu overview: Menu overview
Humidity control
settings
Display and menu overview, continued
Temperature
settings
Lock mode
UnOcc mode
settings
Fan
External
cooling ON/OFF
The relative humidity setpoint can be adjusted by selecting the up and down arrows.
It is not possible to deactive dehumidication using this function.
SetValue
SetValue
Lock
UnOcc
Fan
Cool
The temperature setpoint can be adjusted using this function. Adjust the temperatu-
re by selecting the up and down arrows.
Here you can lock the settings. Setpoint is locked and cannot be adjusted from the
main screen without unlocking.
When UnOcc mode is activated, the dehumidier will run at low fan speed for a time
interval or xed time, depending on which night mode is selected.
To use this function, the current date and time must be set.
This function selects high or low fan speed. It is not possible to deactive the fan
using this function. The EC centrifugal fan utilizes a build-in constant ow regulation
of the airow. The user may dene a min./max. volumetric airow within the speci-
ed range of the given product.
A cooling unit can be connected to reduce the room temperature. Disable/enable
the cooling signal by pressing the button. Select Temperature settings in order to
adjust the temperature setpoint. Remember to activate the cooling control signal
through the menu when a cooling coil is connected.
A heating unit can be connected to ensure that a heating demand is satised. Disa-
ble/enable the heater signal by pressing the button. Select Temperature settings in
order to adjust the temperature setpoint. Remember to activate the heating control
signal through the menu when a heating coil is connected.
External
heating ON/
OFF
Heat
Outdoor air
ON/OFF
Outd. air
An outdoor air duct can be connected to the dehumidier to satisfy minimum out-
door air requirements of min. 15%. Disable/enable the outdoor air ON/OFF signal by
pressing the button.
The signal may be utilised to activate/deactivate a damper and/or exhaust fan within
the room. Remember to activate the outdoor air signal through the menu when the
outdoor air duct is connected.
14