EasyManua.ls Logo

Dantherm CDP 85 - Technical Information; Technical Data

Dantherm CDP 85
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical information: Technical data
en
Technical information
Specication Unit CDP 85 CDP 135 CDP 175
Operational humidity range % RH 40-100 40-100 40-100
Operational temperature
range
°C 15-38 15-38 15-38
Air volume, nominal m³/h 1500 2500 3600
Air volume, range m³/h 500-1500 1200-2500 1500-3600
Dehumidication capacity***
@ 20°C/60% l/24h 56 75 N/A
@ 30°C/60% l/24h 88 165 N/A
Max. external pressure loss *** Pa 300 350 N/A
Power supply V/Hz 1 × 230/50 1 × 230/50 -
- 3 x 400/50 3 x 400/50
Max. power consumption kW 2,0 3,6*/N/A** 6,0
Max. current A 9,5 16,3* / N/A** 9,1
Locked Rotor Amps (LRA) A 21 70*/25** 38
R454C gas weight/CO₂ equiv-
alent
kg/t 1,2 / 0,18 1,5 / 0,22 1,7 / 0,25
GWP (Global Warming
Potential)
- 148
Sound level @ 1 meter (nom-
inal)
dB(A) 58 60 63
Weight kg 130 160 190
Dimensions (w x d x h) mm 1155x725x650 1300x900x850 1400x1010x975
*1x230V, **3x400V, ***Nominal air volume
Technical data
29