Fault nding guide: Fault nding
en
Fault nding guide
If you cannot nd the reason for the fault, switch o the unit immediately in order to prevent
further damage. Contact a service technician or a representative from the manufacturer.
More help
Display text Type Fault Unit behaviour Possible cause Fault nding Solution(s)
No text - - Unit not operating /
non responsive
Power supply interrupt-
ed
12VDC power supply
malfunction
Controller malfunction
- Check fuses in main switch-
board
- Verify that supply voltage is
present at input terminals
- Verify 12VDC output from
PSU
Replace / re-connect
supply fuse(s)
Replace 12VDC PSU
Replace controller
No text - - Display dark or white
with no text or graphic
Dehumidier operat-
ing normally
Display malfunction Restart controller Replace controller
- - No fault Excessive fan noise Inlet/outlet clogged
Excessive back pressure
Verify if lter is clogged
Verify if inlet/outlet has been
restrained
Verify dampers are open (if
installed)
Verify back pressure is within
specied limits
Unresrict air inlet /
outlet
Low Temp. Info No fault Unit in standby Ambient temperature at
RH sensor is too low
-Check actual ambient tem-
perature
-Read measured ambient
temperature in live data
menu view
Unit will restart when
ambient temperature
is within operating
limits
High Temp Ambient temperature at
RH sensor is too high
C. Sensor
E. Sensor
RH Sensor
Alarm Sensor
failure
Sensor failure can
result in irregular
behavior, LP Error or
HP Error
Sensor malfunction Read sensor value in ‘live data
view
Verify temperature sensor
resistance (ohm)*
Verify sensor wire integrity
Replace sensor
Use this table to localize and solve a possible problem or fault:Fault nding