Fault nding guide: Fault nding
en
Display
text
Type Fault Unit behaviour Possible cause Fault nding Solution(s)
LP Error Alarm LP
Error
No or limited condensate
draining from dehumid-
ier
LP Error can be periodical-
ly present
Low ambient tempera-
ture and/or humidity can
result in limited conden-
sation of water
Conrm compressor is running
Conrm fan is running
Conrm solenoid valve is closed (no hissing sound
from valve)
Wait for room tem-
perature/humidity to
increase
Solenoid valve leak Hissing from solenoid valve
Voltage at solenoid valve coil when there is no ice on
evaporator coil
Excercise valve by means
of external magnet or
by applying 230VAC to
valve coil
Replace solenoid valve
Precondition of refriger-
ant leak or TEV failure
See above See above
HP Error Alarm HP
Error
Periodic HP Error
Unit seemingly operating
normally, fault condition
will disappear
Persistant HP Error
Unit blocked for restart
Fan failure Restart unit
Verify fan is working.
If fan switches o for no apparent reason it can be
caused by the internal overload protection
Replace fan
Air inlet/outlet clogged
Coil(s) clogged
Verify dampers are open (if installed)
Verify if inlet and/or outlet are clogged/restrained
Verify if coils are clogged
Unrestrict inlet/outlet
HP temperature sensor
fault
Verify temperature sensor resistance (ohm) Replace temperature
sensor
Condenser coil clogged Inspect condensor coil ns for dust/debris. Clean condenser coil
*Measure the resistance between the two wires coming from the NTC temperature sensor. Resistance should be within the range from 190kΩ - 0,14kΩ corresponding to