24
MENU - To display SUB-MENU 3-2: MODE AND STAGE RESPONSE TIME
Display will read: 3-2 MODE & STAGE RESPONSE TIME
The MODE AND STAGE RESPONSE TIME is a time-based differential over which the processor does not
respond to any changes in temperature or humidity. This includes different functions as well as staging of
individual functions.
SELECT - To display current setting
Display will read:
3-2 MODE & STAGE RESPONSE TIME
RESPONSE TIME: n MINUTE
SELECT or - To change current setting
(Mode and Stage Response Time is adjustable 1 to 5 minutes, in 1 minute increments. Factory setting is
1 minute. Test mode is also an available setting. Test mode allows immediate movement from one function
to another without delay. This should only be used during testing and not left as a operational setting)
MENU - To view SUB-MENU 3-3: COMPRESSOR LEAD/LAG SEQUENCE
Display will read: 3-3 COMPRESSOR LEAD/LAG SEQUENCE
SELECT - To display current setting
Display will read:
3-3 COMPRESSOR LEAD/LAG SEQUENCE
LEAD/LAG SEQUENCE: AUTOMATIC
For the menu item there are three selections:
AUTOMATIC - Changes lead compressors every 168 hours.
1 LEAD
2 LEAD
SELECT or - To change current setting
Factory setting is AUTOMATIC on dual compressor units. In Automatic mode the compressor lead/lag
sequence will change lead compressor every 168 hours of operation.
MENU - To view SUB-MENU 3-4: SYSTEM START DELAY
System Start Delay provides programmable start delay to minimize total in rush current
with multiple unit applications.
Display will read: 3-4 SYSTEM START DELAY
SELECT or - To change current setting
Display will read:
3-4 SYSTEM START DELAY
UNIT STARTS mm:ss AFTER POWER ON
Start delay ranges from 5 seconds to 10 minutes in 5 second intervals. Each time the select button is
pressed the delay will change by 5 seconds.
Factory setting is: 00:05