25
MENU - To view SUB-MENU
3-5: RESET EQUIPMENT RUNTIMES
SELECT - Display will read:
3-5 RESET EQUIPMENT RUNTIME
BLOWER: nnnn HOURS
Continue to press SELECT button to scroll thru the list. The following can be viewed:
CONDENSER: REHEAT STRIP 3:
COMPRESSOR 1: HUMIDIFIER:
COMPRESSOR 2: DEHUMIDIFICATION:
COMPRESSOR 3: ENERGY SAVER COOLING:
COMPRESSOR 4: CHILLED WATER COOLING:
REHEAT STRIP 1: RESET ALL TO ZERO RUNTIMES
REHEAT STRIP 2:
NOTE: Any component can be changed to zero hours. When viewing, press the SILENCE
button to reset a selection to zero hours. To reset all values scroll to the, “RESET ALL TO ZERO
RUNTIMES” menu selection and press the MENU or .
MENU - To view SUB-MENU 3-6: AUTOMATIC SELF-TEST ACKNOWLEDGMENT
If the Self-Test Acknowledge is programmed to “ON”, it will permit the processor to proceed through
the Diagnostic Self-Test even if a failure is detected without pressing the MENU button. It will
allow the unit to start.
SELECT - To view current mode
Display will read: AUTOMATIC SELF-TEST ACKNOWLEDGE: ON
OR
AUTOMATIC SELF-TEST ACKNOWLEDGE: OFF
SELECT or - To change the setting from ON to OFF or OFF to ON.
Factory setting is: OFF
MENU - To view SUB-MENU 3-7 COMPRESSOR SUPPLEMENTS TO E-SAVER
Allows selection of simultaneous Energy Saver and compressor operation. (Optional discharge air
sensor is required.)
SELECT - To view current mode
Display will read: 3-7 COMPRESSOR SUPPLEMENTS TO E-SAVER
ENERGY SAVER NOT AVAILABLE
or SUPPLEMENT E-SAVER WITH 1 COMPRESSOR
or
SUPPLEMENT E-SAVER WITH 2 COMPRESSORS
or
SUPPLEMENT ENERGY SAVER WITH NO COMPRESSORS
SELECT or - To change current setting
Factory setting is: SUPPLEMENT ENERGY SAVER WITH TWO COMPRESSORS
NOTE: After startup,
the service techni-
cian should set sub-
menu 3-6 to ON.