26
NOTE: If the optional discharge air sensor is not installed, the display will read:
DISCHARGE TEMP SENSOR NOT INSTALLED
MENU - To view SUB-MENU 3-8 ENERGY SAVER LOCK-OUT TIME
Display will read: 3-8 ENERGY SAVER LOCK-OUT TIME
SELECT - To view current mode
Display will read: 3-8 ENERGY SAVER LOCK-OUT TIME
LOCKOUT TIME: nn MINUTES
SELECT or - To change current setting
Factory setting is 15 minutes. Lockout time is adjustable from 15 to 60 minutes in 15 minute increments.
MENU - To view SUB-MENU 3-9 DEHUMIDIFICATION MODE
Allows selection for number of compressors to be used in dehumidifi cation mode and temperature or
dehumidifi cation controlled priority.
Display will read: 3-9 DEHUMIDIFICATION MODE
SELECT or - To view current setting
Display will read: 3-9 DEHUMIDIFICATION MODE and one of the following messages:
DEHUMIDIFICATION OFF
or 1 COMPRESSOR & WITHIN REHEAT LIMITS
or 2 COMPRESSORS & WITHIN REHEAT LIMITS
or 1 COMPRESSOR & NO REHEAT LIMITS
or 2 COMPRESSORS & NO REHEAT LIMITS
NOTE: Unit supplied without reheat will display the following message:
NO REHEAT, DEHUMIDIFICATION NOT ALLOWED
SELECT or - To change current setting.
Factory setting is: DEHUMIDIFICATION MODE IS:
1 COMPRESSOR & WITHIN REHEAT LIMITS
MENU - To view SUB-MENU 3-10: POWER PROBLEM OR RESTART MODE
Display will read: 3-10 POWER PROBLEM OR RESTART MODE
SELECT or - To view current setting
Display will read: 3-10 POWER PROBLEM OR RESTART MODE
AUTOMATIC: NO MESSAGE OR ALARM
or AUTOMATIC: MESSAGE, AUDIO ALARM & RELAY
or MANUAL: MESSAGE, AUDIO ALARM & RELAY
Factory setting is: AUTOMATIC: NO MESSAGE OR ALARM
NOTE: If set for MANUAL, the unit must be MANUALLY RESTARTED after a power outage.