MENU - To view SUB-MENU 3-11: SCHEDULED NORMAL MAINTENANCE
Display will read: 3 - 11 SCHEDULED NORMAL MAINTENANCE
SELECT or - To view current setting
Display will read: 3 - 11 SCHEDULED NORMAL MAINTENANCE
MAINTENANCE DUE MESSAGE: OFF
or MAINTENANCE DUE MESSAGE EVERY: nnn HRS
Maintenance can be scheduled from 1 to 1000 hours in 1 hour increments.
SELECT or - To entry number of hours.
Factory setting is: MAINTENANCE DUE MESSAGE: OFF
MENU - To view SUB-MENU 3-12: TEMPERATURE SCALE
Display will read: 3 - 12 TEMPERATURE SCALE
SELECT or - To view current setting
Display will read: 3 - 12 TEMPERATURE SCALE
DISPLAY TEMPERATURE IN: FAHRENHEIT
SELECT or - To change current setting
There are two choices: Fahrenheit and Centigrade
Factory setting is: Fahrenheit
MENU - To view SUB-MENU 3-13: FAN MODE - This submenu does not display when RFM is OFF
Display will read: 3 - 13 FAN MODE
SELECT or - To view current setting
Display will read: 3- 13 FAN MODE
FAN MODE: CONTINUOUS
SELECT or - Change setting, options are:
CONTINUOUS (Fan runs continuously.)
or AUTO (Fan runs only when there is a call for cooling, heating, humidi cation or
dehumidi cation. Auto is only used in RFM mode, primarily ceiling applications.)
Factory setting is: CONTINUOUS
MENU - To view SUB-MENU 3-14: OVERRIDE REQUEST (When unit is in night setback mode and
you want the unit operating.)
Display will read: 3- 14 OVERRIDE REQUEST
SELECT or - To view current setting
Display will read: 3 - 14 OVERRIDE REQUEST
OVERRIDE REQUEST: NO
MENU - To view SUB-MENU 3-15: HUMIDITY ANTICIPATION
T
his submenu does not displa
y
when RFM is
O
FF