28
Display will read: 3 - 15 HUMIDITY ANTICIPATION
SELECT or - To view current setting
Display will read: 3 - 15 HUMIDITY ANTICIPATION
HUMIDITY ANTICIPATION: OFF
The two choices: OFF or ON
In the “ON” mode, the DAP III changes setpoints to minimize humidifi cation and
dehumidifi cation cycles. See page
64 for complete explanation.
SELECT or - To change current setting
Factory setting is: OFF
MENU - To view SUB-MENU 3-16: HUMIDIFICATION DESATURATION CYCLE
Display will read: 3-16 HUMIDIFICATION DESATURATION CYCLE
SELECT or - To see current setting
Display will read: 3-16 HUMIDIFCATION DESATURATION CYLCE
DUTY CYCLE: NOT USED
SELECT or - To view current setting
There are 19 choices:
DUTY CYCLE: NOT USED or
2 MIN OFF EVERY 5 MIN ON or 3 MIN OFF EVERY 5 MIN ON or 5 MIN OFF EVERY 5 MIN ON
2 MIN OFF EVERY 10 MIN ON or 3 MIN OFF EVERY 10 MIN ON or 5 MIN OFF EVERY 10 MIN ON
2 MIN OFF EVERY 15 MIN ON or 3 MIN OFF EVERY 15 MIN ON or 5 MIN OFF EVERY 15 MIN ON
2 MIN OFF EVERY 20 MIN ON or 3 MIN OFF EVERY 20 MIN ON or 5 MIN OFF EVERY 20 MIN ON
2 MIN OFF EVERY 25 MIN ON or 3 MIN OFF EVERY 25 MIN ON or 5 MIN OFF EVERY 25 MIN ON
2 MIN OFF EVERY 30 MIN ON or 3 MIN OFF EVERY 30 MIN ON or 5 MIN OFF EVERY 30 MIN ON
SELECT or - To change current setting
Factory setting is: DUTY CYCLE: NOT USED
MENU - To view SUB-MENU 3-17: E-SAVER TO DX CHANGEOVER DEADBAND
Display will read: 3-17 E-SAVER TO DX CHANGEOVER DEADBAND
If “DUTY CYCLE: NOT USED” is selected, the stan-
dard humidifi cation logic is used. If one of the time
OFF every time ON duty cycles are selected and the
unit is in the cooling mode, the humidifi er will cycle
ON and then OFF based on that selected duty cycle.
During the time the humidifi er is OFF, a status mes-
sage HUMIDIFICATION OFF BY DESATURATION
CYCLE will be displayed as the current status mes-
sage that cycle on the lower line of the LCD display.