SELECT or - To view current setting.
Display will read 3-17 E-SAVER TO DX CHANGEOVER DEADBAND
SET AT: 2.0F
SELECT or - To change setting.
(
E-Saver to DX changeover deadband is adjustable from 2 to 5
o
F. Factory setting is 2
o
F. )
MENU - To view Sub-Menu 3-18: CONSTATN FAN SPEED FOR DX COOLING
Display will read 3-18 CONSTANT FAN SPEED FOR DX COOLING
SELECT or - To view current setting.
Display will read 3-18 CONSTANT FAN SPEED FOR DX COOLING
FAN SPEED: XX%
Constant fan speed for DX cooling is adjustable from 70 to 100%.
Factory setting is 100%.
SELECT or - To view current setting.
MENU - To view Sub-Menu 3-19: CONSTATN FAN SPEED FOR CW COOLING
Display will read 3-19 CONSTANT FAN SPEED FOR CW COOLING
SELECT or - To view current setting.
Display will read 3-19 CONSTANT FAN SPEED FOR CW COOLING
FAN SPEED: 100%
Constant fan speed for CW cooling is adjustable from 60 to 100%.
Factory setting is 100%.
SELECT or - To view current setting.
MENU - To view Sub-Menu 3-20: FAN SPEED CONTROL FOR DX COOLING
Display will read 3-20 FAN SPEED FOR DX COOLING
SELECT or - To view current setting
Display will read 3-20 FAN SPEED CONTROL FOR DX COOLING
FAN SPEED: CONSTANT SPEED
or
CONSTANT STATIC PRESSURE
SELECT or - To change current setting.