45
Display will read: 5-8 WATER VALVE VOLTAGE CONTROL RANGE
SELECT or - To view current setting
Display will read: 5-8 WATER VALVE VOLTAGE CONTROL RANGE
WATER VALVE CONTROL RANGE: 2-10 DC
SELECT or -
To view alternate setting
0-10 DC
4-7 DC
6-9 DC
7-10 DC
Factory setting is: 2-10 DC
MENU - To view next sub-menu
Display will read: 5-9 REVERSE ACTING WATER VALVE
SELECT or - To view current setting
Display will read: 5-9 REVERSE ACTING WATER VALVE
REVERSE ACTING WATER VALVE: NO
OR
REVERSE ACTING WATER VALVE: YES
Factory setting is: NO
SELECT or - To change setting
MENU - To view next sub-menu
Display will read: 5-10 HUMIDIFIER AUTOFLUSH TIMER - (Requires Relay Module)
SELECT or - To view current setting
Display will read: 5-10 HUMIDIFIER AUTOFLUSH TIMER
HUMIDIFIER AUTOFLUSH TIMER NOT USED
SELECT or -
To view alternate setting
FLUSH HUMIDIFIER EVERY 06 HOUR
FLUSH HUMIDIFIER EVERY 12 HOUR
FLUSH HUMIDIFIER EVERY 24 HOUR
- to -
FLUSH HUMIDIFIER EVERY 96 HOUR - in 12 hour increments
Factory setting is: HUMIDIFIER AUTOFLUSH TIMER NOT USED
EXIT - Press EXIT to return to GROUP 5 - CONFIGURATION
EXIT - Press EXIT again to return to Current Operating Functions & Status Display
OR

Other manuals for Data Aire DAP III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire DAP III and is the answer not in the manual?

Data Aire DAP III Specifications

General IconGeneral
BrandData Aire
ModelDAP III
CategorySecurity System
LanguageEnglish

Related product manuals