Display will read: 5-8 WATER VALVE VOLTAGE CONTROL RANGE
SELECT or - To view current setting
Display will read: 5-8 WATER VALVE VOLTAGE CONTROL RANGE
WATER VALVE CONTROL RANGE: 2-10 DC
SELECT or -
To view alternate setting
0-10 DC
4-7 DC
6-9 DC
7-10 DC
Factory setting is: 2-10 DC
MENU - To view next sub-menu
Display will read: 5-9 REVERSE ACTING WATER VALVE
SELECT or - To view current setting
Display will read: 5-9 REVERSE ACTING WATER VALVE
REVERSE ACTING WATER VALVE: NO
OR
REVERSE ACTING WATER VALVE: YES
Factory setting is: NO
SELECT or - To change setting
MENU - To view next sub-menu
Display will read: 5-10 HUMIDIFIER AUTOFLUSH TIMER - (Requires Relay Module)
SELECT or - To view current setting
Display will read: 5-10 HUMIDIFIER AUTOFLUSH TIMER
HUMIDIFIER AUTOFLUSH TIMER NOT USED
SELECT or -
To view alternate setting
FLUSH HUMIDIFIER EVERY 06 HOUR
FLUSH HUMIDIFIER EVERY 12 HOUR
FLUSH HUMIDIFIER EVERY 24 HOUR
- to -
FLUSH HUMIDIFIER EVERY 96 HOUR - in 12 hour increments
Factory setting is: HUMIDIFIER AUTOFLUSH TIMER NOT USED
EXIT - Press EXIT to return to GROUP 5 - CONFIGURATION
EXIT - Press EXIT again to return to Current Operating Functions & Status Display