48
MENU - To view OCTET 4
Display will read: 6-5 ROUTER ADDRESS
ROUTER ADDRESS OCTET 4: 0. 0. 0. 0
MENU - To advance to next sub-menu.
Only displays when protocol (6-2) is set to BACNET
Display will read: 6-6 UDP PORT
SELECT or - To view current setting
6-6 UDP PORT (UDP- User Datagram Protocol)
UDP LISTEN PORT: nnnn
The UDP PORT has a range from 0 to 65535. Hold the SELECT or SELECT button to advance to
desired setting.
Factory setting is: 47808
MENU - To advance to next sub-menu - Only displays when protocol (6-2) is set to MODBUS TCP/IP.
Display will read: 6-7 TCP PORT
SELECT or - To view current setting
Display will read: 6-7 TCP PORT TCP LISTEN PORT: nnn
The TCP PORT has a range from 0 to 65535. Hold the SELECT or SELECT button to advance to
desired setting.
Factory setting is: 502
MENU - To advance to sub-menu 6-8 BAUD RATE.
Display will read: 6-8 BAUD RATE
SELECT or - To view current setting
6-6 BAUD RATE
SET AT: 9600
SELECT or - To change setting
Selections are: 9600, 19200, 38400, 57600, 76800, and 115200.
Factory setting is: 9600
MENU - To advance to next sub-menu 6-9 NETWORK ID (BACnet MAC addess)
Display will read: 6-9 NETWORK ID
SELECT or - To view current setting
Display will read: 6-9 NETWORK ID
NETWORK ID: 001
Sub menu 6-6 only displays when
protocol is BACnet or MODbus
TCP/IP.