48
MENU - To view OCTET 4
Display will read: 6-5 ROUTER ADDRESS
ROUTER ADDRESS OCTET 4: 0. 0. 0. 0
MENU - To advance to next sub-menu.
Only displays when protocol (6-2) is set to BACNET
Display will read: 6-6 UDP PORT
SELECT or - To view current setting
6-6 UDP PORT (UDP- User Datagram Protocol)
UDP LISTEN PORT: nnnn
The UDP PORT has a range from 0 to 65535. Hold the SELECT or SELECT button to advance to
desired setting.
Factory setting is: 47808
MENU - To advance to next sub-menu - Only displays when protocol (6-2) is set to MODBUS TCP/IP.
Display will read: 6-7 TCP PORT
SELECT or - To view current setting
Display will read: 6-7 TCP PORT TCP LISTEN PORT: nnn
The TCP PORT has a range from 0 to 65535. Hold the SELECT or SELECT button to advance to
desired setting.
Factory setting is: 502
MENU - To advance to sub-menu 6-8 BAUD RATE.
Display will read: 6-8 BAUD RATE
SELECT or - To view current setting
6-6 BAUD RATE
SET AT: 9600
SELECT or - To change setting
Selections are: 9600, 19200, 38400, 57600, 76800, and 115200.
Factory setting is: 9600
MENU - To advance to next sub-menu 6-9 NETWORK ID (BACnet MAC addess)
Display will read: 6-9 NETWORK ID
SELECT or - To view current setting
Display will read: 6-9 NETWORK ID
NETWORK ID: 001
Sub menu 6-6 only displays when
protocol is BACnet or MODbus
TCP/IP.

Other manuals for Data Aire DAP III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire DAP III and is the answer not in the manual?

Data Aire DAP III Specifications

General IconGeneral
BrandData Aire
ModelDAP III
CategorySecurity System
LanguageEnglish

Related product manuals