EasyManua.ls Logo

Datakom D-200 MK2 - Ac Voltage Inputs

Datakom D-200 MK2
135 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 17 -
Measurement method:
True RMS
Sampling rate:
8000 Hz
Harmonic analysis:
up to 31th harmonic
Input voltage range:
14 to 300 VAC
Minimum voltage for
frequency detection:
15 VAC (Ph-N)
Supported topologies:
3 ph 4 wires star
3 ph 3 wires delta
3ph 4 wires delta
2ph 3 wires L1-L2
2ph 3 wires L1-L3
1 ph 2 wires
Measurement range:
0 to 330VAC ph-N (0 to 570VAC ph-ph)
Common mode offset:
max 100V between neutral and BAT-
Input impedance:
4.5M-ohms
Display resolution:
1VDC
Accuracy:
0.5% + 1 digit @ 230VAC ph-N (±2VAC ph-N)
0.5% + 1 digit @ 400VAC ph-ph (±3VAC ph-ph)
Frequency range:
DC to 650Hz
Frequency display
resolution:
0.1 Hz
Frequency accuracy:
0.2% + 1 digit (±0.1 Hz @ 50Hz)