EasyManua.ls Logo

Datakom D-200 MK2 - Page 44

Datakom D-200 MK2
135 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 44 -
Term
Function
Technical data
Description
51
GENERATOR CONTACTOR
Relay output, 16A-AC
This output provides energy to the
generator contactor. If the generator
phases do not have acceptable voltage or
frequency values, the generator contactor
will be de-energized. In order to provide
extra security, the normally closed contact
of the mains contactor should be serially
connected to this output.
52
GEN-L1
Generator phase
inputs, 0-300V-AC
Connect the generator phases to these
inputs. The generator phase voltages
upper and lower limits are programmable.
54
GEN-L2
56
GEN-L3
58
GENERATOR NEUTRAL
Input, 0-300V-AC
Neutral terminal for the generator phases.
Term
Function
Technical data
Description
59
CURR_1+
Current transformer
inputs, 5A-AC
Connect the generator current transformer
terminals to these inputs.
Do not connect the same current
transformer to other instruments otherwise
a unit fault will occur.
Connect each terminal of the transformer
to the unit’s related terminal.
Do not use common terminals. Do not use
grounding.
Correct polarity of connection is vital.
The rating of the transformers should be
identical for each of the 3 phases.
The secondary winding rating shall be 5
Amperes. (ex: 200/5 Amps).
60
CURR_1-
61
CURR_2+
62
CURR_2-
63
CURR_3+
64
CURR_3-
Term
Function
Technical data
Description
65
MAINS NEUTRAL
Input, 0-300V-AC
Neutral terminal for the mains phases.
67
MAINS-L3
Mains phase inputs,
0-300V-AC
Connect the mains phases to these inputs.
The mains voltages upper and lower limits
are programmable.
69
MAINS-L2
71
MAINS-L1
72
MAINS CONTACTOR
Relay output, 16A-AC
This output provides energy to the mains
contactor. If the mains phases do not have
acceptable voltages, the mains contactor
will be de-energized. In order to provide
extra security, the normally closed contact
of the generator contactor should be
serially connected to this output.

Table of Contents

Related product manuals