D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 79 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Low Frequency
Warning Limit
%
F-100
F+100
V-15%
If the genset frequency goes under this
limit when feeding the load, this will
generate a GENSET LOW
FREQUENCY warning.
Genset Low Frequency
Shutdown Limit
%
F-100
F+100
F-20%
If the genset frequency goes under this
limit when feeding the load, this will
generate a GENSET LOW
FREQUENCY shutdown alarm and the
engine will stop.
Genset High Frequency
Warning Limit
%
F-100
F+100
F+15%
If the genset frequency goes over this
limit when feeding the load, this will
generate a GENSET HIGH
FREQUENCY warning.
Genset High Frequency
Shutdown Limit
%
F-100
F+100
F+20%
If the genset frequency goes over this
limit when feeding the load, this will
generate a GENSET HIGH
FREQUENCY shutdown alarm and the
engine will stop.
Genset Frequency Fail
Timer
sec
0
10
1
If the genset frequency goes outside of
the limits during this timer, a genset
frequency fault will occur.
Low Battery Voltage
Warning Limit
V-DC
5.0
35.0
12.0
If the battery voltage falls below this
limit, this will generate a LOW
BATTERY warning.
Low Battery Voltage
Shutdown Limit
V-DC
5.0
35.0
9.0
If the battery voltage falls below this
limit, this will generate a LOW
BATTERY shutdown alarm and the
engine will stop.
High Battery Voltage
Warning Limit
V-DC
5.0
35.0
29.0
f the battery voltage goes over this limit,
this will generate a HIGH BATTERY
warning.
High Battery Voltage
Shutdown Limit
V-DC
5.0
35.0
30.0
If the battery voltage goes over this
limit, this will generate a HIGH
BATTERY shutdown alarm and the
engine will stop.
Battery Voltage Fail
Timer
sec
0
10
3
If the battery voltage goes outside of the
limits during this timer, a battery voltage
fault will occur.
Genset Voltage
Unbalance Limit
%
0
100
0.0
If any genset phase voltage differs from
the average more than this limit, it will
generate a Voltage Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
Genset Voltage
Unbalance Action
-
0
3
0
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
16.2. ELECTRICAL PARAMETERS GROUP (continued)