D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 83 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
GCB Alarm Level
-
0
1
0
0: shutdown alarm
1: loaddump alarm
Genset MCB Fail Timer
sec
0
600
2.0
If a genset MCB feedback input is
defined and if the genset MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Genset Phase Order
Check Enable
-
0
1
0
0: genset phase order checking
disabled
1: if genset phase order is faulty, then a
genset phase order fail loaddump alarm
is given.
Multi Load Subtract
Power Level
kW
0
65000
0
When the genset active power goes
over this limit, the controller will start
substracting load as described in
chapter Five Step Load Management.
Multi Load Add Power
Level
kW
0
65000
0
When the genset active power goes
below this limit, the controller will start
adding load as described in chapter
Five Step Load Management.
Multi Load Subtract Start
Delay
sec
0
36000
0
If the load stays over the Multi Load
Substract Power Level parameter
during this timer, then 1 step of load is
substracted.
Multi Load Subtract Wait
Delay
sec
0
36000
0
This is the minimum period between
two load subtract operations.
Multi Load Add Start
Delay
sec
0
36000
0
If the load stays below the Multi Load
Add Power Level parameter during this
timer, then 1 step of load is added.
Multi Load Add Wait
Delay
sec
0
36000
0
This is the minimum period between
two load add operations.
Excess power Warning
Limit
kW
0
50000
0
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
16.2. ELECTRICAL PARAMETERS GROUP (continued)