D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 88 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Service-2 Engine Hours
hours
0
5000
250
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-2
engine hours.
Service-2 Period
month
0
24
6
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-2
Period.
Service-2 Alarm Level
-
0
3
0
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
Service-3 Engine Hours
hours
0
5000
250
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-3
engine hours.
Service-3 Period
month
0
24
6
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-3
Period.
Service-3 Alarm Level
-
0
3
0
0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
J1939 Enable
-
0
1
0
0: The J1939 port is inoperative.
1: The analog measurements (oil,
temp, and rpm) are picked up from
the ECU. If the ECU communication
is lost, then the engine will be
stopped.
J1939 Engine Brand
-
0
15
0
0: GENERIC
1: CUMMINS
2: DETROIT DIESEL
3: DEUTZ
4: JOHN DEERE
5: PERKINS
6: VOLVO
7: CATERPILLAR
8: SCANIA
9: IVECO
10: MTU-MDEC
11: BOSCH
12: BAUDOUIN
Other values: Reserved. Do not use.