EasyManua.ls Logo

Datakom D-700 MK3 - Page 100

Datakom D-700 MK3
218 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-700 MK3 User Manual Firmware V-16.8
- 100 -
Synchronization Fail
Set if the phase and voltage synchronization is not successful before the
expiration of Synchronization Fail Timeout
Busbar Voltage Fail
Set if busbar voltages are not within limits and busbar voltage above Dead
Bus Limit during 5 seconds, when the master requests the slave to close
the genset contactor to the busbar.
Busbar Freq. Fail
Set if busbar frequency is not within limits and busbar voltage above Dead
Bus Limit during 5 seconds, when the master requests the slave to close
the genset contactor to the busbar.

Table of Contents

Related product manuals