D-700 MK3 User Manual Firmware V-16.8
- 115 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Modbus Master Active
-
0
1
0
This is the parameter to enable modbus
master/slave operation of controller
through rs-485 terminal.
0: modbus slave controller
1: modbus master controller
Remote Battery Charge
Voltage
V-DC
0.0
70.0
0.0
This parameter is functional for battery
backup operation with DKG-359 device.
If mains is not available, and measured
battery group voltage is less than
Remote Battery Charge Voltage, then
the controller will start the genset.
Remote Battery Charge
Time
min
0.0
600.0
0.0
Genset will run and GC will be on
during this timer, unless mains recovers
or the battery gets fully charged.
Remote Battery
Discharge Limit
Ah
0.0
1000.0
0.0
The battery group will discharge until
reaching the Remote Battery Discharge
Limit before the D-series controller runs
the genset and energize the GC.
17.1. CONTROLLER CONFIGURATION GROUP (continued)