EasyManua.ls Logo

Datakom D-700 MK3 - Page 122

Datakom D-700 MK3
218 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-700 MK3 User Manual Firmware V-16.8
- 122 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Busbar Fail Timer
sec
0
30
2.0
When a genset closes to the Busbar, if
the mater genset controller does detect
the Busbar voltage at the expiration of
this period, a “BUSBAR FAIL” fault
condition will occur.
Busbar Ready Timer
sec
0
30
2.0
This is the delay after all generators
close to the busbar and before the
master genset controller acknowledges
“Busbar ready” signal.
Multi Load Subtract
Power Level
kW
0
65000
0
When the genset active power goes
over this limit, the controller will start
substracting load as described in
chapter Five Step Load Management.
Multi Load Add Power
Level
kW
0
65000
0
When the genset active power goes
below this limit, the controller will start
adding load as described in chapter
Five Step Load Management.
Multi Load Substract
Start Delay
sec
0
36000
0
If the load stays over the Multi Load
Substract Power Level parameter
during this timer, then 1 step of load is
substracted.
Multi Load Substract
Wait Delay
sec
0
36000
0
This is the minimum period between
two load subtract operations.
Multi Load Add Start
Delay
sec
0
36000
0
If the load stays below the Multi Load
Add Power Level parameter during this
timer, then 1 step of load is added.
Multi Load Add Wait
Delay
sec
0
36000
0
This is the minimum period between
two load add operations.
Excess power Warning
Limit
kW
0
50000
0
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
Earth Current
Transformer Primary
Amp
1
5000
500
This is the rated value of current
transformers at the earth CT inputs.
Earth Current Alarm Limit
Amp
0
50000
0
If earth current goes over this limit when
feeding the load, this will generate a
overcurrent fault condition.
Earth Current Alarm
Level
-
-
-
1
0: loaddump
1: warning
Earth Current Fault Delay
sec
0
120
0
If earth current is over the limit during
this timer, earth current alarm will occur.
Over Current Timer
sec
0
120
0
If any of the phase currents is over the
limit during this timer, an overcurrent
fault will occur.
Voltage Unbalance Timer
sec
0
120
5
If any genset phase voltage differs from
the average more the limit during this
timer, it will generate Voltage
Unbalance fault condition.
17.2. ELECTRICAL PARAMETERS GROUP (continued)

Table of Contents

Related product manuals