D-700 MK3 User Manual Firmware V-16.8
- 152 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Voltage Up/Down
Pulse Maximum Duration
msec
0
2000
0
This parameter defines the maximum
pulse width in voltage pulse control mode.
If this parameter is set to zero then no
maximum pulse width is used.
Voltage Up/Down
Pulse Delay
msec
20
1000
20
This parameter defines the minimum
pulse delay between two of voltage
up/down control pulses.
Return to Mid-Point
-
0
1
0
This parameter controls the “Return to
Mid-point” output relay function.
0: no return to mid-point output
1: return to mid-point output active during
stop timer.
Reactive Load Sharing
Pulse Period
msec
0
5000
10
In reactive load sharing, this is the period
between two voltage up/down pulses.
Reactive Load Sharing
Start Limit
%
0
100
0.0
This is the minimum reactive power
percentage in order to activate voltage
up/down pulses.