DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 25 -
No Description Adjustment Range Factory set
P13 Automatic Restart
0:Disable (the unit will power-up
always in STOP mode)
1: Enable (the unit will power-up
with the same mode as the
power-down instant)
0
P14
Temperature for Pressure
Compensation
0 ... (P09)
While the air end temperature is
below this limit, instead of P04
Stop Pressure, P05+(P04-P05)/4
value is used.
Thus the compressor stops
before reaching Stop Pressure .
0 °C
P15 Delay Between Relays 20 ... 250 200ms
P16 Voltage Unbalance Ratio 0 ...20 5 %
P17
Temp. 2 Sensor operation
mode
0:Disable
1:Absolute temperature
2:Differential temperature
If this parameter is set to 0, the
P18, P19, P20 and P22
parameters will not be displayed.
0
P18 Top range Temp. 2 Sensor (P19+2) ... 200 130 °C
P19
Temp. 2 Sensor High Limit
(Delta Alarm Limit)
(P20+2) ... (P18-2)
(Temperature differential alarm
Limit)
110 °C
P20
Low Alarm/Delta Warning
Temp. 2
-40 ... (P19-2)
(Temperature differential warning
Limit)
-10 °C
P21
Alarm/Warning Duration
time
1 ... 600 10 sec
P22
Offset value Temp. 2
Sensor
-10:+10 0 °C
P23 Star Timer 2 ... 20 7 sec
P24 Star /Delta transition Timer 10 ... 50 35 ms
P25 Timer before loading 1 ... 120 1 sec
P26 unload timer 0 ... 10 2 min