DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 30 -
No Description Adjustment Range Factory set
P83
Pressure sensor-2 low
pressure alarm limit (if
adjusted to 0.0 then no
alarm is given)
0.. (P79-0.5) 0
P84 Reserved - 0
P85 Reserved - 0
P86 Reserved - 0
P87 Reserved - 0
P88 Service security selection
0: Service request gives warning
only
1:Service request stops the
compressor as explained in
chapter_5.
0
P88 Reserved - 0
P89
Variable Hour counting
method
0: Fixed hour counting coefficient
1: Variable hour counting method
Refer chapter 6.3 for more
details.
0
P90 Pressure Dot Display
0: Enable
1: Disable
If this parameter is set to 0, the
pressure is displayed in xx.x
format. This format is useful for
display in bars.
If this parameter is set to 1, the
pressure is displayed in xxx
format. This format is useful for
display in psi.
0