Table 2: Configurable input functions
Configurable input function Value in the controller Digital input*
Not used 0
Remote start/stop 6
Low fuel level warning 5
Low oil pressure warning 8
Low oil pressure shutdown 2
High oil temperature warning 7
High oil temperature shutdown 1
High coolant temperature shutdown 9
Auxiliary alarm shutdown (Emergency stop) 4
*You can fill in the number of the corresponding digital input configured for this function in your system.
4.1.3 Changing parameters using the front panel
To change parameters by using the front panel:
1. Press
and simultaneously to go into parameter setting mode.
2. The access code screen opens. The four-digit access code prevents unauthorised people from changing
the CGC 200 setup via the front buttons. The factory default code is 2000. To enter the access code:
1. Press to increase the value of the digit where the cursor is blinking. You can use to de-
crease the value.
2. Press to move to the next digit.
3. When the cursor is on the last digit, press
to enter the access code. The parameter list now
opens.
3. Press or to get to the parameter you want to change.
4. Press
to start editing the parameter.
1. Press to increase the value of the digit where the cursor is blinking. You can use to de-
crease the value.
2. Press to move to the next digit.
3. When the cursor is on the last digit, press
to enter the change.
4. After the change is entered, none of the parameter digits will blink. You can now press or
to get to the next parameter you want to change.
5. When you have finished changing parameters, press
to exit parameter setting mode.
The table below lists the functions of the push-buttons in parameter setting mode.
CGC 200 Operator's manual 4189340770
UK
Parameters
DEIF A/S Page 19 of 43