4.1.2 Parameter list
The parameters used by CGC 200 that can be changed from the controller front panel are listed in the table
below.
Param-
eter
num-
ber
Parameter
name
Range De-
fault
value
Value
chos-
en*
Description
P00 Auto start delay 0 to 3600 s 1 Timer for starting using the Auto start
signal
P01 Auto stop delay 0 to 3600 s 1 Timer for stopping after the Auto start
signal is removed
P02 Start attempts 1 to 10 3 Number of start attempts in one start se-
quence
P03 Start prepare 0 to 300 s 0 Timer for start prepare
P04 Start on time 3 to 60 s 8 Timer for starter ON time during crank-
ing
P05 Start off time 3 to 60 s 10 Timer for starter OFF time before a new
start attempt is made
P06 Initial inhibit de-
lay
1 to 60 s 10 Timer for bypassing frequency and volt-
age shutdown during starting
P07 Idle start 0 to 3600 s 0 Timer for idle speed after starting
P08 GB close delay 3 to 3600 s 10 Timer for generator breaker close after
frequency and voltage OK
P09 Cooldown time 3 to 3600 s 10 Cooling down time
P10 Idle stop 0 to 3600 s 0 Timer for idle speed before stopping
P11 Extended stop 0 to 120 s 20 Timer for extended stop
P12 Stop failure 0 to 120 s 0 Maximum allowable time for stopping
the genset
P13 Number of teeth 10 to 300 118 The number of teeth on flywheel. This is
only used when MPU is selected as run-
ning detection (see P40).
P14 Number of gen.
poles
2 to 32 4 The number of genset poles. This is
used in the frequency calculation.
P15 Hz/V OK delay 0 to 20.0 s 10.0 Voltage and frequency OK delay after
starting of genset
P16 G U > 30 to 360 V 264 Generator over-voltage protection
P17 G U < 30 to 360 V 196 Generator under-voltage protection
P18 G RPM < 0 to 6000
RPM
1200 Generator under-speed protection, if
running detection (see P40) is RPM in-
put only
CGC 200 Operator's manual 4189340770
UK
Parameters
DEIF A/S Page 15 of 43