Param-
eter
num-
ber
Parameter
name
Range De-
fault
value
Value
chos-
en*
Description
P19 G RPM > 0 to 6000
RPM
1710 Generator over-speed protection, if run-
ning detection (see P40) is RPM input
only
P20 G f < 0 to 75.0 Hz 45.0 Generator under-frequency protection
P21 G f > 0 to 75.0 Hz 57.0 Generator over-frequency protection
P22 Running feed-
back timer
0 to 20.0 s 5.0 Maximum allowable time for running de-
tection (see P40)
P23 U > aux. term.1 12.0 to 40.0 V 33.0 High battery supply voltage
P24 U < aux. term.1 4.0 to 30.0 V 8.0 Low battery supply voltage
P25 Relay 01 0 to 6 4 See Table 1: Configurable output func-
tions
P26 Relay 02 0 to 6 1
P27 Relay 03 0 to 6 2
P28 Digital input 1 0 to 10 5 See Table 2: Configurable input func-
tions
P29 Digital input 1
timer
0 to 20.0 s 10.0
P30 Digital input 2 0 to 10 6
P31 Digital input 2
timer
0 to 20.0 s 2.0
P32 Digital input 3 0 to 10 4
P33 Digital input 3
timer
0 to 20.0 s 1.0
P34 Digital input 4 0 to 10 2
P35 Digital input 4
timer
0 to 20.0 s 3.0
P36 Digital input 5 0 to 10 1
P37 Digital input 5
timer
0 to 20.0 s 10.0
P38 Default genset
mode
0 to 2 0 0: Stop mode
1: Manual start
2: Auto start
P39 Display pass-
word
0 to 9999 2000 Prevents unauthorised changes to pa-
rameters using the controller front panel
CGC 200 Operator's manual 4189340770
UK
Parameters
DEIF A/S Page 16 of 43