EasyManua.ls Logo

Deif CGC 200 - Page 17

Deif CGC 200
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Param-
eter
num-
ber
Parameter
name
Range De-
fault
value
Value
chos-
en*
Description
P40 Running detect. 0 to 2 2 0: RPM
1: Genset frequency
2: RPM and frequency (running detec-
tion is present when the value required
to remove the starter is met for either
engine speed (see P41) or genset fre-
quency (see P42))
For RPM, P13 and P41 must be de-
fined.
For frequency, P42 must be defined.
P41 Remove starter
RPM
0 to 3000
RPM
360 Minimum engine speed required for re-
moval of the starter and running detec-
tion
P42 Remove starter
Hz
10.0 to 30.0
Hz
14.0 Minimum genset frequency required for
removal of the starter and running de-
tection
*You can fill in the values chosen for your system.
CGC 200 Operator's manual 4189340770
UK
Parameters
DEIF A/S Page 17 of 43

Other manuals for Deif CGC 200

Related product manuals