EasyManua.ls Logo

Dell EMC XC Core XC6515 - Environmental Specifications

Dell EMC XC Core XC6515
159 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 68. Supported rear video resolution options (continued)
Resolution Refresh rate (Hz) Color depth (bits)
1280 x 1024 60 8, 16, 32
1360 x 768 60 8, 16, 32
1440 x 900 60 8, 16, 32
1600 x 900 60 8, 16, 32
1600 x 1200 60 8, 16, 32
1680 x 1050 60 8, 16, 32
1920 x 1080 60 8, 16, 32
1920 x 1200 60 8, 16, 32
Environmental specifications
NOTE: For additional information about environmental certifications, refer to the
Product Environmental Datasheet
located with the Manuals & Documents on https://www.dell.com/support.
Operational climatic range category A2
Table 69. Operational climatic range category A2
Allowable continuous operations
Temperature ranges for altitude <900 meters (<2,953 feet) 10 to 35°C (50 to 95°F) with no direct sunlight on the platform
Humidity percent ranges (Non-condensing at all times) 8% RH with -12°C minimum dew point to 80% RH with 21°C
(69.8°F) maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/300 meters (1.8°F/984
feet) above 900 meters (2,953 feet)
Operational climatic range category A3
Table 70. Operational climatic range category A3
Allowable continuous operations
Temperature ranges for altitude <900 meters (<2,953 ft) 5°C- 40°C (41°F-104°F) with no direct sunlight on the platform
Humidity percent ranges (Noncondensing at all times) 8% RH with -12°C minimum dew point to 85% RH with 24°C
(75.2°F) maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 meters (1.8°F/574
feet) above 900 meters (2,953 feet)
Operational climatic range category A4
Table 71. Operational climatic range category A4
Allowable continuous operations
Temperature ranges for altitude < 900 meters (<2953 feet) 5 to 45°C (41 to 113°F) with no direct sunlight on the platform
Humidity percent ranges (Non-condensing at all times) 8% RH with -12°C minimum dew point to 90% RH with 24°C
(75.2°F) maximum dew point
Technical specifications 137

Table of Contents

Related product manuals