Expanded operating temperature specications
Table 26. Expanded operating temperature
Expanded operating temperature Specications
Continuous operation 5°C to 40°C at 5% to 85% RH with 29°C
dew point.
NOTE: Outside the standard
operating temperature (10°C to
35°C), the system can operate
continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C and 40°C,
de-rate maximum allowable temperature by
1°C per 175 m above 950 m (1°F per 319
ft).
≤ 1% of annual operating hours –5°C to 45°C at 5% to 90% RH with 29°C
dew point.
NOTE: Outside the standard
operating temperature (10°C to
35°C), the system can operate
down to –5°C or up to 45°C for a
maximum of 1% of its annual
operating hours.
For temperatures between 40°C and 45°C,
de-rate maximum allowable temperature by
1°C per 125 m above 950 m (1°F per 228
ft).
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported in the System Event
Log.
Fresh Air Operation
Fresh Air operation restrictions
Processors with a TDP greater than 105 W are not supported.
Support for processors of 85 W and below without PERC restrictions
3.5" HDD conguration is not supported.
114 mm heat sink is required for the processor in CPU1 socket.
Intel Ethernet Server Adapter X710-DA2 for Open Compute Project (OCP) is not supported.
X8 M.2 SATA card is not supported.
NVMe SSD is not supported.