Table 24. Maximum shock specifications (continued)
Maximum shock Specifications
Storage Six consecutively executed shock pulses in the positive and negative x,
y, and z axes (one pulse on each side of the system) of 71 G for up to
2 ms.
Table 25. Maximum altitude specifications
Maximum altitude Specifications
Operating
3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Table 26. Operating temperature de-rating specifications
Operating temperature de-rating Specifications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above
950 m (3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above
950 m (3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above
950 m (3,117 ft).
Standard operating temperature
Table 27. Standard operating temperature specifications
Standard operating temperature Specifications
Continuous operation (for altitude less than 950 m or
3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
Expanded operating temperature
Table 28. Expanded operating temperature specifications
Expanded operating temperature Specifications
Continuous operation 5°C40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C35°C),
the system can operate continuously in temperatures as low as 5°C
and as high as 40°C.
For temperatures between 35°C40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
1% of annual operating hours 5°C45°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C35°C),
the system can operate down to 5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228
ft).
NOTE: When operating in the expanded temperature range, system performance may be impacted.
24 Technical specifications