Table 16. Serial Connection Settings
Setting Value
Emulation VT220
Column Mode 132
Line Wrapping Off
Connection Serial Port
Connection Type Direct
Baud Rate 115200
Parity None
Data Bits 8
Stop Bits 1
Flow Control XON/XOFF
Related links
Troubleshooting the Serial Connection to a Storage Controller Module
Configure the Bottom Storage Controller
Configure the bottom storage controller (storage controller 2) with the information provided in the pre-
installation documents.
Prerequisites
Create a serial connection from a computer to the storage controller, as described in Establish a Serial
Connection to the Bottom Storage Controller.
About this task
Configure the bottom storage controller with the higher HSN and IP addresses for the Ethernet
management interface (eth0) and Baseboard Management Controller (BMC).
Figure 85. Storage Controllers
1. Top storage controller (storage controller 1) 2. Bottom storage controller (storage controller
2)
CAUTION: Wait for the top storage controller to finishing booting before configuring the bottom
storage controller. If you configure the bottom storage controller before the top storage
controller has finished booting, the bottom storage controller may not configure correctly.