Menu 2-06 Automatic summer/winter changeover
Default seing: Automatic changeover
No automatic changeover
Automatic changeover
Menu 2-07 Days until boiler/heat pump service reminder
Must be reset aer every service.
Default seing: “---” (function o).
Adjustable "---" (function o) or from 1 to 365 days
Menu 2-08 Control time base
The control quality depends on parameters like the building's insulation, the number of radiators or the ooring
type. The “Tips” column in the following table will help you select the seing that is appropriate for your setup.
Default seing: 15 minutes.
Choice of
control type
Heater
type
Generator
type
Tips
15 minutes
(2)
Radiator
Boiler/Heat pump
(1)
Increase the time base to extend generator
run times and thus prevent starting up so
oen.
30 minutes
(2)
Radiator
Underoor heating
Boiler/Heat pump
(1)
45 minutes
(2)
Underoor heating
Boiler/Heat pump
(1)
Reduce the time base if you notice big
dierences in temperature.
60 minutes
(2)
Underoor heating Heat pump
(1)
All or nothing/
On-o
Radiator
Underoor heating
Heat pump
(1)
Only recommended if the PID control isn't
satisfactory.
Recommended hysteresis value: between 0.4
and 1
Oven range
heating
Hysteresis value: follow the value
recommended by the range's manufacturer
(1) The control is ed with anti-short cycle protection to suppress start or stop requests when they are too short.
The anti-short cycle duration is 10% of the time base selected (e.g.: if the time base is set to 30 minutes, the anti-short
cycle will be 3 minutes, i.e. the thermostat will not accept any start or stop requests that are under 3 minutes).
(2) PID control time base:
Menu 2-11 Hysteresis seing (if 2-08 = tor)
Default seing: 0.4°C.
Adjusts from 0.2°C to 2°C,
in increments of 0.1°C.
Menu 2-06 does not appear if your Tybox is
linked with the Tydom app (menu 1-10 = 1).
If you don't want to use this function, leave
the seing on “---”.
Example:
Setpoint 20°C. Hysteresis 0.4°C.
Heating request if T° measured <19.8°C.
Heating shuts down if T° measured> 20.2°C.